DEHNguard modular NL

  • Prewired complete unit consisting of a base part and plug-in protection modules
  • Energy coordination with other arresters of the Red/Line product family
  • High discharge capacity due to heavy-duty zinc oxide varistors/spark gaps
  • High reliability due to "Thermo Dynamic Control" SPD monitoring device
  • Easy replacement of protection modules without tools due to module locking system with module release button
  • Vibration and shock-tested according to EN 60068-2

DEHNguard M TNS 275 NL (FM)

Modular surge arrester for TN-S systems, neutral conductor on the left side

2 Products

Part No. 952402 DG M TNS 275 NL

GTIN 4013364110014, Customs tariff No. (EU): 85363030, Gross weight: 436.70 g, PU: 1.00 pc(s)


Images

Additional information

Certificates

 

Technical data

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 20 kA
Max. discharge current (8/20 µs) (Imax ) 40 kA
Voltage protection level (UP ) ≤ 1.5 kV
Voltage protection level at 5 kA (UP ) ≤ 1 kV
Max. mains-side overcurrent protection 125 gG
Approvals KEMA, VDE, UL

Product 952402 was added to Notepad.

Product 952402 was added to the cart.

Part No. 952407 DG M TNS 275 NL FM

GTIN 4013364110021, Customs tariff No. (EU): 85363030, Gross weight: 440.00 g, PU: 1.00 pc(s)


Images

Additional information

Certificates

 

Technical data

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 20 kA
Max. discharge current (8/20 µs) (Imax ) 40 kA
Voltage protection level (UP ) ≤ 1.5 kV
Voltage protection level at 5 kA (UP ) ≤ 1 kV
Max. mains-side overcurrent protection 125 gG
Approvals KEMA, VDE, UL
Type of remote signalling contact changeover contact

Product 952407 was added to Notepad.

Product 952407 was added to the cart.


DEHNguard M TT 275 NL (FM)

Modular surge arrester for TT and TN-S systems (3+1 configuration), neutral conductor on the left side.

2 Products

Part No. 952312 DG M TT 275 NL

GTIN 4013364113992, Customs tariff No. (EU): 85363030, Gross weight: 441.60 g, PU: 1.00 pc(s)


Images

Additional information

Certificates

 

Technical data

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) [L-N] (UC ) 275 V (50 / 60 Hz)
Max. continuous operating voltage (a.c.) [N-PE] (UC ) 255 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 20 kA
Max. discharge current (8/20 µs) (Imax ) 40 kA
Voltage protection level [L-N] (UP ) ≤ 1.5 kV
Voltage protection level [L-N] at 5 kA (UP ) ≤ 1 kV
Voltage protection level [N-PE] (UP ) ≤ 1.5 kV
Max. mains-side overcurrent protection 125 gG
Approvals KEMA, VDE, UL

Product 952312 was added to Notepad.

Product 952312 was added to the cart.

Part No. 952317 DG M TT 275 NL FM

GTIN 4013364114005, Customs tariff No. (EU): 85363030, Gross weight: 445.10 g, PU: 1.00 pc(s)


Images

Additional information

Certificates

 

Technical data

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) [L-N] (UC ) 275 V (50 / 60 Hz)
Max. continuous operating voltage (a.c.) [N-PE] (UC ) 255 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 20 kA
Max. discharge current (8/20 µs) (Imax ) 40 kA
Voltage protection level [L-N] (UP ) ≤ 1.5 kV
Voltage protection level [L-N] at 5 kA (UP ) ≤ 1 kV
Voltage protection level [N-PE] (UP ) ≤ 1.5 kV
Max. mains-side overcurrent protection 125 gG
Approvals KEMA, VDE, UL
Type of remote signalling contact changeover contact

Product 952317 was added to Notepad.

Product 952317 was added to the cart.


DEHNguard M TN 275 NL (FM)

Modular surge arrester for single-phase 230 V TN systems, neutral conductor on the left side

2 Products

Part No. 952202 DG M TN 275 NL

GTIN 4013364109964, Customs tariff No. (EU): 85363030, Gross weight: 241.80 g, PU: 1.00 pc(s)


Images

Additional information

Certificates

 

Technical data

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 20 kA
Max. discharge current (8/20 µs) (Imax ) 40 kA
Voltage protection level (UP ) ≤ 1.5 kV
Voltage protection level at 5 kA (UP ) ≤ 1 kV
Max. mains-side overcurrent protection 125 gG
Approvals KEMA, VDE, UL

Product 952202 was added to Notepad.

Product 952202 was added to the cart.

Part No. 952207 DG M TN 275 NL FM

GTIN 4013364109971, Customs tariff No. (EU): 85363030, Gross weight: 246.70 g, PU: 1.00 pc(s)


Images

Additional information

Certificates

 

Technical data

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 20 kA
Max. discharge current (8/20 µs) (Imax ) 40 kA
Voltage protection level (UP ) ≤ 1.5 kV
Voltage protection level at 5 kA (UP ) ≤ 1 kV
Max. mains-side overcurrent protection 125 gG
Approvals KEMA, VDE, UL
Type of remote signalling contact changeover contact

Product 952207 was added to Notepad.

Product 952207 was added to the cart.


DEHNguard M TT 2P 275 NL (FM)

Modular surge arrester for single-phase 230 V TT and TN systems (1+1 configuration), neutral conductor on the left side

2 Products

Part No. 952112 DG M TT 2P 275 NL

GTIN 4013364109995, Customs tariff No. (EU): 85363030, Gross weight: 241.10 g, PU: 1.00 pc(s)


Images

Additional information

Certificates

 

Technical data

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) [L-N] (UC ) 275 V (50 / 60 Hz)
Max. continuous operating voltage (a.c.) [N-PE] (UC ) 255 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 20 kA
Max. discharge current (8/20 µs) (Imax ) 40 kA
Voltage protection level [L-N] (UP ) ≤ 1.5 kV
Voltage protection level [L-N] at 5 kA (UP ) ≤ 1 kV
Voltage protection level [N-PE] (UP ) ≤ 1.5 kV
Max. mains-side overcurrent protection 125 gG
Approvals KEMA, VDE, UL

Product 952112 was added to Notepad.

Product 952112 was added to the cart.

Part No. 952117 DG M TT 2P 275 NL FM

GTIN 4013364110007, Customs tariff No. (EU): 85363030, Gross weight: 244.80 g, PU: 1.00 pc(s)


Images

Additional information

Certificates

 

Technical data

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) [L-N] (UC ) 275 V (50 / 60 Hz)
Max. continuous operating voltage (a.c.) [N-PE] (UC ) 255 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 20 kA
Max. discharge current (8/20 µs) (Imax ) 40 kA
Voltage protection level [L-N] (UP ) ≤ 1.5 kV
Voltage protection level [L-N] at 5 kA (UP ) ≤ 1 kV
Voltage protection level [N-PE] (UP ) ≤ 1.5 kV
Max. mains-side overcurrent protection 125 gG
Approvals KEMA, VDE, UL
Type of remote signalling contact changeover contact

Product 952117 was added to Notepad.

Product 952117 was added to the cart.


DEHNguard M SN1731

Modular surge arrester for single-phase 230 V TT and TN systems (1+1 configuration), neutral conductor on the left side

1 Product

Part No. 952112 DG M TT 2P 275 NL

GTIN 4013364109995, Customs tariff No. (EU): 85363030, Gross weight: 241.10 g, PU: 1.00 pc(s)


Images

Additional information

Certificates

 

Technical data

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) [L-N] (UC ) 275 V (50 / 60 Hz)
Max. continuous operating voltage (a.c.) [N-PE] (UC ) 255 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 15 kA
Max. discharge current (8/20 µs) (Imax ) 40 kA
Voltage protection level [L-N] (UP ) ≤ 1.5 kV
Voltage protection level [L-N] at 5 kA (UP ) ≤ 1.25 kV
Voltage protection level [N-PE] (UP ) ≤ 1.5 kV
Max. mains-side overcurrent protection 125 gG
Approvals VdS

Product 952112 was added to Notepad.

Product 952112 was added to the cart.


back to top